Dixell XR60CX-5N1C1 Digital Thermostat Controller with Defrost Compressor Control of Evaporator Fans 230V/50-60Hz Programmable-Commercial for Refrigeration
- ...s are used to control the interval between defrost cycles (IdF), its maximum length (MdF) and two defrost modes: timed or controlled by the evaporator?s probe (P2P).At the end of defrost dripping time is started, its length is set in the FSt parameter. With FSt =0 the dripping time is disabled..
- Forced activation of fans This function managed by the Fct parameter is designed to avoid short cycles of fans, that could happen when the controller is switched on or after a defrost, when the room air warms the evaporator. Functioning: if the difference of temperature between the evaporator and the room probes is more than the value of the Fct parameter, the fans are switched on. With Fct=0 the function is disabled..
- Cyclical activation of the fans with compressor off. When Fnc = c-n or c-Y (fans in parallel to the compressor), by means of the Fon and FoF parameters the fans can carry out on and off cycles even if the compressor is switched off. When the compressor is stopped the fans go on working for the Fon time. With Fon =0 the fans remain always off, when the compressor is off..
- Suitable for applications on medium or low temperature ventilated refrigerating units.XR60CX-5N1C1,230V/50-60Hz.